S7 Read (s7-read)

Reads variables from a SIEMENS S7 PLC over RFC1006 / ISO-on-TCP. Three modes cover the typical industrial polling patterns:

Inputs Outputs
0 (static), 1 (dynamic), 0 or 1 (block) 1

Modes

static (default) cyclically polls a fixed list of variables at pollInterval. The most common pattern for dashboards and trending.

dynamic triggers one read per incoming message. The variable list comes from the message (msg.variables or the msg.address+dataType convenience form); when the message carries no override, the configured sidebar list acts as a fallback, so you can use dynamic as "static-on-trigger" or fully msg-driven.

block reads a contiguous byte range from one area in raw form. Pipe the result into s7-parser to decode multiple fields at once — typical when a single DB carries a tightly-packed measurement record. With triggerOnInput=true the cyclic poll is additive to on-demand reads (poll continues; messages force an extra read between ticks).

Configuration

Field Default Description
plc ID of the referenced s7-plc config node.
mode static static / dynamic / block.
variables [] Variables list, see Variables.
block Block-mode descriptor, see Block mode.
outputShape auto Variables-mode output: single (1 var) / array / object. Defaults to single for 1 var, object for 2+.
pollInterval 1000 Static / block mode polling period in milliseconds.
emitOnChange false Suppress duplicate emits when the read result is unchanged.
emitOnError false Emit a separate error message on read failure (in addition to routing through the Catch node).
topicTemplate derived Optional topic format. Placeholders: <plc-name>, <address>, <name>, <area>, <db>, <start>, <length>.

Variables

Field Required Description
name optional Display name. Defaults to the address. Used as the key in outputShape=object.
address yes Siemens-style address, see Address syntax.
dataType yes TIA-Portal type, see Data types.
scale optional Multiplicative scale: value = raw × scale + offset. Default 1.
offset optional Additive offset, applied after scaling. Default 0.

Scaling is skipped automatically for non-numeric types (string, wstring, raw, date, dt, ldt, dtl, wchar, counter, timer).

Block mode

Field Default Description
area DB DB / M / I / Q.
db DB number. Required when area=DB.
start 0 Start byte offset within the area.
length Byte count to read. Hard upper bound is the negotiated PDU minus 22 bytes header (≈ 460 B at PDU 480). Larger blocks are auto-split into multiple AGReadArea calls and concatenated.
triggerOnInput false Adds an input port that fires an extra read on every message (additive on top of the cyclic poll). Override area / db / start / length per message via msg.s7.*.

Address syntax

S7 addresses follow the Siemens engineering tool notation. The full table lives in NODE_S7.md; the practical summary:

Form Example Compatible dataType
DB<n>.DBX<byte>.<bit> DB10.DBX2.3 bool
DB<n>.DBB<byte> DB10.DBB4 byte / char / sint / usint
DB<n>.DBW<byte> DB10.DBW6 word / int / uint / wchar / date
DB<n>.DBD<byte> DB10.DBD0 dword / dint / udint / real / time / tod
DB<n>.DBL<byte> DB10.DBL16 lreal / lint / ulint / lword / ltime / ltod / ldt / dt (8 B)
DB<n>.DTL<byte> DB3.DTL171 dtl (12 B)
DB<n>.STRING<byte>.<max> DB1.STRING50.20 string
DB<n>.WSTRING<byte>.<max> DB1.WSTRING50.20 wstring
M<byte>.<bit>, MB/MW/MD M0.3, MD16 bit / byte / word / dword
I<byte>.<bit>, IB/IW/ID I0.0, IB1 bit / byte / word / dword
Q<byte>.<bit>, QB/QW/QD Q0.0, QB1 bit / byte / word / dword
C<n> / T<n> C5, T3 int / counter / timer

DBL and DTL are LOOPZE coinages — Siemens addresses 8- and 12-byte types symbolically in the engineering tool, so there is no canonical wire form for them. The names follow the existing DBB / DBW / DBD pattern.

Optimized DBs are not reachable via S7 — see the s7-plc note. The parser rejects symbolic addresses with a hint pointing at OPC UA.

Data types

The codec covers the full SIEMENS TIA-Portal type system. The complete reference table with per-CPU support is in NODE_S7.md; the headline:

  • Bitfields: bool, byte, word, dword, lword
  • Integers (signed): sint, int, dint, lint
  • Integers (unsigned): usint, uint, udint, ulint
  • Floats: real, lreal
  • Durations (decode → integer ms / ns): timer (S5TIME), time, ltime, tod, ltod
  • Date / DateTime (decode → ISO date or RFC3339Nano string): date, dt, ldt, dtl
  • Characters / strings: char, wchar, string, wstring
  • Other: counter (BCD; read-only), raw (byte block in the parser)

Numerical durations decode to plain integers (ms or ns) because downstream JSON consumers prefer numbers over stringified durations. Date / DT / LDT / DTL decode to RFC3339Nano UTC strings so timestamps round-trip cleanly through JSON.

Outgoing message

Variables modes (outputShape=object, default for ≥ 2 vars)

{
  "topic": "s7/press-line-2",
  "payload": {
    "BoilerTemp":   84.7,
    "PressureBar":   5.2,
    "AlarmActive": false
  },
  "s7": {
    "plc": "Press Line 2",
    "variables": [
      { "name": "BoilerTemp",   "address": "DB10.DBD0", "dataType": "real", "value": 84.7 },
      { "name": "PressureBar",  "address": "DB10.DBD4", "dataType": "real", "value":  5.2 },
      { "name": "AlarmActive",  "address": "M0.0",      "dataType": "bool", "value": false }
    ]
  }
}

outputShape=single puts the bare value in msg.payload (only legal with exactly 1 variable). outputShape=array emits the full per-variable list as the payload. The msg.s7 metadata is identical across shapes.

Block mode

{
  "topic": "s7/press-line-2/db3",
  "payload": [129, 66, 214, 200, 202, 254, 207, 199, ...],
  "s7": {
    "plc":    "Press Line 2",
    "area":   "DB",
    "db":     3,
    "start":  0,
    "length": 256
  }
}

msg.payload is []int (not []byte) so the Debug panel and any JSON consumer downstream see the bytes as decimal numbers rather than a base64-encoded string. s7-parser accepts both shapes.

Multi-variable reads

When several variables fit one PDU, the manager bundles them into a single AGReadMulti round-trip. For PDU 480 (S7-1500 default) that is roughly 460 bytes of payload — comfortably enough for 20+ scalars. Bundling is automatic; authoring N variables in the sidebar list is the same wire cost as authoring the equivalent block read for that case.

For very large reads (> PDU), use block mode — the manager auto-splits the area into multiple AGReadArea calls and concatenates the results before emitting.

Status

  • Green — connected · <interval> (static) / connected · idle (dynamic).
  • Yellow — connecting... / reconnecting... from the PLC config.
  • Red — disconnected plus the underlying transport error.