S7 Parser (s7-parser)

Decodes raw S7 byte blocks into structured objects (parse direction) or builds raw byte blocks from objects (encode direction). The layout is configured declaratively as a list of fields and is shared by both directions — pair the parser with s7-read block mode upstream (parse) or s7-write block mode downstream (encode).

Inputs Outputs
1 1

Why a parser node?

A typical TIA-Portal DB packs a measurement record into a tightly-laid-out byte range:

DB100 (record layout)
  byte  0   REAL    setpoint
  byte  4   REAL    actual
  byte  8   INT     mode
  byte 10.0 BOOL    running
  byte 10.1 BOOL    alarm
  byte 11   BYTE    quality

You can read the six fields as six s7-read variables — bundled into one AGReadMulti round-trip when they fit a PDU. Or you can read the entire 12-byte range in block mode and decode it client-side with this node. The block path is the right call when:

  • The record is larger than one PDU (auto-splits into multiple AGReadArea calls — much cheaper than 50+ individual variable reads).
  • You want symmetric read + write of the same record (the layout is reusable for both directions).
  • The DB is not yours — third-party PLCs often expose contiguous records that you'd rather decode in one place than scatter across N variables.

Configuration

Field Default Description
action auto auto (sniff input shape) / parse (force decode) / encode (force build). Auto: object input → encode; everything else → parse.
parseFrom payload Message field carrying the byte block on parse.
encodeFrom payload Message field carrying the structured object on encode.
blockLength 0 Fixed output buffer size in bytes (0 = derive from layout extent). Larger than the layout pads with zeros; smaller than required is rejected at deploy.
preserveBytes false Parse only — also forward the raw bytes as msg.bytes ([]int).
layout [] Ordered list of field descriptors, see Layout.

Layout

Each entry describes one field in the byte block:

Field Required Description
name yes Output key (parse) or input key (encode). Duplicates are rejected at deploy.
offset yes Buffer offset (0-based, relative to the block, not the PLC address). Integer for byte-aligned types; dotted byte.bit for bool (e.g. "12.3").
type yes TIA type — see s7-read data types. Plus raw (byte slice with length).
length when type=string / wstring / raw Max length in characters (string/wstring) or byte count (raw).
signed optional For byte / word / dword: interpret as signed. Inherently-signed types (int, dint, lint) reject this flag.
scale optional Multiplicative scale: value = raw × scale + offset. Default 1. Skipped for non-numeric types.
valueOffset optional Additive offset, applied after scaling. Default 0.
unit optional Display-only label shown in the layout editor. Not propagated to the message.

Offsets are buffer-relative: a layout starting at offset 0 is portable across DBs. The downstream s7-write block.start positions the buffer at the right PLC byte. (The parser deliberately does not auto-set msg.s7.start — that would silently break the invariant that encode and parse use the same offset semantics.)

Examples

Decode a sensor block from s7-read

Layout for the record above:

- { name: setpoint, offset: 0,    type: real }
- { name: actual,   offset: 4,    type: real }
- { name: mode,     offset: 8,    type: int  }
- { name: running,  offset: 10.0, type: bool }
- { name: alarm,    offset: 10.1, type: bool }
- { name: quality,  offset: 11,   type: byte }

Pipe s7-read (block mode, DB100, length 12) into the parser. Output:

{
  "payload": {
    "setpoint": 70.0,
    "actual":   68.5,
    "mode":     1,
    "running":  true,
    "alarm":    false,
    "quality":  255
  }
}

Build a write buffer for s7-write block mode

Same layout, action=encode. Upstream Function emits:

{ "payload": { "setpoint": 75.0, "mode": 2, "running": true } }

The parser emits msg.payload = []int (the wire bytes), with missing keys (actual, alarm, quality) left at zero. Pipe into s7-write (block mode, DB100, start 0). Sparse-zero semantics let you author one layout that handles partial updates without resetting unmentioned fields — provided your downstream tolerates the zero-fill.

Pack a BOOL status word

Multiple BOOLs sharing one host byte are OR-aggregated on encode, so a status word is straightforward:

- { name: alarm,   offset: "0.0", type: bool }
- { name: warn,    offset: "0.1", type: bool }
- { name: running, offset: "0.7", type: bool }

Input { alarm: true, running: true } produces 0x81 (bits 0 and 7 set). Missing keys default to false, matching sparse-zero behaviour for non-bool fields.

Auto mode

action=auto dispatches based on input shape:

  • msg.payload is a map / object → encode
  • msg.payload is a byte array (or array of numbers) → parse

Auto is convenient when one parser node serves both directions of a single layout. Use parse or encode to force one path when the input shape is ambiguous (e.g. a JSON-decoded byte array that happens to look like an object key-value pair to an observer).

Output shape

Parse direction

{
  "payload": { "setpoint": 70.0, "actual": 68.5, "mode": 1, "running": true, ... },
  "bytes":   [66, 140, 0, 0, 66, 137, 0, 0, 0, 1, 0x80, 255]
}

msg.bytes is only added when preserveBytes=true.

Encode direction

{
  "payload": [66, 140, 0, 0, 66, 137, 0, 0, 0, 1, 0x80, 255],
  "bytes":   [66, 140, 0, 0, 66, 137, 0, 0, 0, 1, 0x80, 255]
}

msg.payload is []int (decimal numbers in JSON) so the Debug panel renders them legibly. msg.bytes mirrors the same value for symmetry with parse direction.

Notes

  • Big-endian throughout — the canonical S7 wire order regardless of CPU family.
  • No timezone metadata on date/time wire types. dt / ldt / dtl decode to RFC3339Nano UTC strings; the wall-clock vs. UTC distinction is documented per type in the data types reference.
  • Overlapping fields produce a slog.Warn at deploy (BOOLs sharing one host byte are excluded — that's the canonical Siemens status-word pattern).

See also