S7 PLC config node (s7-plc)

Connection-config node for a SIEMENS S7 PLC over RFC1006 / ISO-on-TCP (port 102). Holds host, port, rack/slot, manages the gos7 client lifecycle, exposes the negotiated PDU size and the reconnect state to every read/write node that references it, and powers the Test Connection button in the configuration panel.

s7-plc is a config node — no canvas element. It is created from the "+" button next to the PLC dropdown on any S7 read/write node and stored in the workspace alongside the flows. Multiple S7 nodes that reference the same PLC share one TCP connection, mirroring how real S7 PLCs serialise access per connection.

Configuration

Field Default Description
name Display name. Used in topics (s7/<name>/...) and as the PLC label in dropdowns.
host PLC IP address or hostname.
port 102 TCP port. The bundled demo PLC uses 1102 to avoid sudo.
connectionType s7-1200-1500 CPU family preset — drives the rack/slot defaults.
rack / slot derived Manual override (only honoured when connectionType=custom).
timeout 5000 Connect / read / write timeout in milliseconds.
reconnectDelay 2000 Backoff between reconnect attempts after the link drops, in milliseconds.

Connection types

Preset Rack Slot When to use
s7-1200-1500 0 1 S7-1200 and S7-1500 CPUs (default).
s7-300-400 0 2 S7-300, S7-400, ET 200S CPU.
logo 1 0 LOGO! 0BA7/0BA8 and S7-200 Smart.
custom Anything else — set rack / slot manually.

Optimized DBs (TIA Portal)

S7-1200 and S7-1500 CPUs default to Optimized block access for new DBs. Optimized DBs are not reachable via the S7 wire protocol — only via OPC UA with symbolic addressing. To use the S7 nodes, un-tick Optimized block access on each DB you want to address with classical wire forms (DB10.DBD0, M0.0, …).

The address parser explicitly rejects symbolic forms (DB1.MotorSpeed) with a hint pointing to OPC UA, so the misconfiguration surfaces at deploy rather than as a confusing runtime error.

Test Connection

The PLC config panel exposes a Test Connection button that performs a round-trip Connect → GetCpuInfoGetOrderCode → Disconnect against the configured host. The result includes the PLC's reported firmware version and order code so you can confirm the right CPU is reachable before deploying the flows.

The endpoint is intentionally tolerant of placeholder strings returned by software simulators (the bundled demo PLC returns Snap7 defaults like "Snap7-Server" instead of a real article number).

Status propagation

The PLC's connection state is propagated to every referencing node's status pill:

  • Green — connected · <pdu> B PDU
  • Yellow — connecting... / reconnecting...
  • Red — disconnected: <reason>

A flow with five s7-read nodes against the same PLC sees all five turn red simultaneously when the link drops, and all five recover together on the next successful reconnect.

Demo PLC

The repo bundles a python-snap7-based demo PLC at demo/s7-server/ with pre-filled DB1 / DB2 / DB3 / DB10 plus animated values for cyclic polling tests. Run it via make demo-s7; stop with make demo-s7-stop.

The demo PLC carries two compatibility patches over upstream python-snap7 1.4 — see its README for the details. Both are scoped to the demo and do not affect the production client.

See also

  • S7 Read — cyclic / on-demand / block-mode reads.
  • S7 Write — variable, msg-driven, or block-mode writes.
  • S7 Parser — decode block-mode bytes into structured objects (and back).